Power Quality for Data Centers

Measure at the main incomer, UPS AC input and cooling drive input. Use those readings to assess feeder-level harmonic filtering and dynamic reactive compensation on the main bus.

Data center server aisle
Illustrative facility photograph

Data center reference configuration

In this example, the UPS input meets the project target, cooling drives dominate harmonic current, and reactive demand varies at the main bus. Evaluate feeder-level AHF and bus-level SVG, with an analyzer for the baseline and commissioning checks.

Low-voltage distribution and connection pointsOne supply path shown. Assess A and B paths and each source mode individually.
Utility / standby supplyVia source transfer where fitted, such as ATS
LV main switchboardIncomer measurement point
  • UPS input feederMeasure at the AC input · supplies IT loads via UPS
  • Cooling drive feederMeasure at drive input · evaluate shunt AHF
  • Bus compensation branchSeparate shunt SVG where justified by measured kVAr

Distribution and compensation referencesSchneider Electric · Data center reference designEaton · Data center harmonicsCIRCUTOR · Static var generator manual

  1. Measure the incomer and two feeders

    Record voltage distortion, harmonic current by order, kW, kVAr and power factor at the LV incomer, UPS AC input and cooling drive input. Compare representative light and peak loads on each supply path.

    Online Power Quality Analyzer
  2. Evaluate an AHF on the cooling feeder

    If the measurements locate the dominant harmonic current on the cooling feeder, evaluate a shunt filter there. If several feeders contribute, compare bus-level filtering. Size from the harmonic current to compensate and review the current transformer measurement boundary.

    Sucyc-AHF Active Harmonic Filter (IGBT)
  3. Evaluate an SVG on the main bus

    Where fundamental reactive demand varies with load, use the measured kVAr profile to assess dynamic compensation. Review existing capacitor banks and utility or generator operation, especially the risk of leading power factor at light load.

    Static Var Generator (SVG)

How to verify the result

Harmonics
Compare voltage distortion and targeted harmonic currents before and after mitigation at the same measurement points, with the same supply mode and comparable load. Evaluate compliance at the applicable point of common coupling (PCC).
Reactive power
Check kVAr and power factor through representative light-load and peak-load periods. Review leading and lagging behavior in the agreed operating modes.
Operation and transfer
During the approved commissioning window, check alarms and coordination with the UPS, backup supply and existing compensation. Record transfer events separately from steady-state measurements.

Harmonic limits at the PCCIEEE 519

Prepare a project enquiry

  • Single-line diagram with A/B supply paths, transfer equipment and candidate connection points
  • Main and feeder measurements, harmonic spectra and the reactive power trend
  • UPS, cooling drive and existing compensation equipment details
Request a Quote