AC and DC Power Supply Surge Protection
Select separate surge protective devices (SPDs) for an industrial cabinet’s AC supply and non-PV DC feeders based on circuit voltage, earthing and existing protection.

AC supply and DC feeder SPD selection
Consider a control cabinet fed from an AC distribution board. A cabinet power supply feeds a separate DC circuit serving field devices. Identify the equipment to protect and assess exposure at the AC supply and at any DC feeder that runs out to the field.
Separate the AC and DC circuits on the drawing
Trace the incoming AC supply, the cabinet power supply and the DC feeders. Note which cables run outdoors or between cabinets and identify any surge protection already fitted.
Evaluate the AC supply SPD
For the AC supply, compare the system voltage and earthing arrangement with the documented application limits of SCD20EF385G404. Confirm its voltage protection level (Up) and compatibility with the specified upstream protection.
Review DC supply protection separately
For a non-PV DC feeder, check the DC surge protective device against the feeder’s continuous operating voltage, circuit configuration and required voltage protection level.
Verify AC and DC protection at handover
At commissioning, verify the specified SPD models at the AC and DC positions shown on the approved drawing. Record their initial status and check that any alarm signal specified by the project reaches the monitoring system.
Prepare a project enquiry
- Distribution and control cabinet drawings showing the AC input and DC feeders
- AC system voltage and earthing, plus DC voltage range and polarity arrangement
- Cable routes, the equipment to be protected and any existing surge and upstream protection