Sucyc-AHF Active Harmonic Filter (IGBT)
The IGBT-based Sucyc-AHF compensates 2nd–50th order harmonics and supports reactive power compensation and three-phase load balancing. Module options range from 30–200 A, depending on system voltage.

Key specifications

| Rated voltage | 200 / 400 / 480 / 690 / 800 V |
|---|---|
| Rated frequency | 50 / 60 Hz (−10% to +10%) |
| Capacity options | 30 / 50 / 75 / 100 / 150 / 200 A per module200/400 V: 30–200 A. 480 V: 50–200 A. 690/800 V: 100 A. |
| Wiring type | Three-phase, three- or four-wire |
| Mounting options | Wall-mounted / rack-mounted / floor-standing |
Product highlights
- Rated voltage options from 200 to 800 V
- 2nd–50th order harmonic compensation, including the 2nd, 5th, 7th, 11th and 13th orders
- Total response time below 10 ms
- Parallel modules with optional N+1 redundancy
Technical specifications
- Rated voltage
- 200 / 400 / 480 / 690 / 800 V
- Rated frequency
- 50 / 60 Hz (±10%)
- Compensation current per module
- 200/400 V: 30–200 A. 480 V: 50–200 A. 690/800 V: 100 A.
- Harmonic compensation range
- 2nd–50th orders
- Current THD (THDi) after filtering
- <5% under typical conditions
- Total response time
- <10 ms
Additional specifications
- Unit efficiency
- ≥97.5%
- Wiring configurations
- Three-phase three-wire or four-wire
- Mounting options
- Rack, wall or floor mounting
- Enclosure protection
- IP20
Topology, controls and communications
A three-level IGBT topology uses DSP and FPGA digital control with FFT harmonic analysis. The filter also supports reactive power compensation and three-phase load balancing.
- Switching frequency
- 20 kHz typical
- Power factor control
- −1 to +1 (inductive and capacitive)
- Overload capacity
- 110% continuous, 120% for 1 minute
- Operator display
- Optional 1.8-, 4.3- or 7-inch HMI
- Communications
- RS485 and CAN, plus RJ45 for inter-module connections
- Current transformer sensing
- Open- or closed-loop sensing, according to the project and its parallel control design.
- Equipment protection
- Overvoltage, undervoltage, overcurrent, overcompensation and inverter bridge faults
Installation conditions and parallel capacity
Use the system voltage, required compensation current and cabinet conditions to confirm the module combination.
- Per-module compensation current
- 200/400 V: 30–200 A. 480 V: 50–200 A. 690/800 V: 100 A.
- Cabinet capacity
- Up to 5 modules and 1,000 A per cabinet, subject to configuration
- Operating temperature
- −25 to 55 °C, with derating above 45 °C
- Relative humidity
- 5–95% RH, non-condensing
- Installation altitude
- Derating required above 1,500 m
Model codes and rack dimensions
For Sucyc-AHF-4L-400-100/R, 4L identifies three-phase four-wire, 100 is the rated compensation current in amperes, and R identifies rack mounting. The selection data groups the 200, 400 and 480 V options under the 400 code. Confirm the actual voltage and model when ordering.
Scroll across to see all columns
| Model | Voltage | Current | W × D × H (mm) | Weight |
|---|---|---|---|---|
| Sucyc-AHF-4L-400-100/R | 400 V | 100 A | 440 × 570 × 230 | 35 kg |
| Sucyc-AHF-4L-400-150/R | 400 V | 150 A | 510 × 580 × 250 | 43.5 kg |
| Sucyc-AHF-4L-400-200/R | 400 V | 200 A | 630 × 640 × 250 | 65 kg |
| Sucyc-AHF-4L-690-100/R | 690 V | 100 A | 525 × 620 × 250 | 55 kg |
3L identifies three-phase three-wire. The 690 and 800 V options use their corresponding voltage codes. The standard IGBT designation has no S marker. The SiC designation includes S. W identifies wall mounting, and C identifies floor mounting.
Application conditions to review
- 690/800 V industrial distribution
- Check the supply voltage and measured harmonic current for nonlinear loads such as rolling mills or crushers.
- Production equipment and variable-speed drives
- Measure the spectrum of drives, welders or rectifiers across representative production loads before choosing compensation current.
- Rectifiers and single-phase loads
- Include the 2nd order in the measurement and selection when it is present at the feeder.
- UPS and power conversion equipment
- Review the AC-side measurement points and operating modes for UPS systems, photovoltaic installations or charging equipment.
- HVAC, lighting and lifts
- Review the harmonic spectrum of HVAC drives, LED drivers and lifts at the intended compensation point in a commercial building.
Typical configurations
These examples illustrate how module combinations are selected. Size the actual installation from measured harmonic current, load profile and cabinet conditions.
- 690 V steel or mining distribution
- Four 100 A rack-mounted Sucyc-AHF-4L-690-100/R modules provide a combined nominal compensation current of 400 A.
- 400 V production loads with 2nd-order harmonics
- A three-module configuration with 100 A per module can be evaluated for rectifier and single-phase loads. Check the measured 2nd-order current and the other orders that need compensation.
- 400 V production lines with redundancy
- Evaluate 150 A rack-mounted modules for groups of drives and welders. For N+1, check that the remaining modules can meet the required compensation current with one module unavailable.
Selection questions
How do I choose between the IGBT and SiC variants?
Start with system voltage, available space and the project’s response and efficiency requirements. The IGBT series includes 690 V and 800 V options. Compare the specifications for the exact SiC model for applications with tight space or demanding load changes.
What module current ratings are available at 690 V and 800 V?
Both voltage options use 100 A modules. The 30 A module is available at 200 and 400 V, while 480 V options start at 50 A.
What current THD should I expect after filtering?
The product specification lists THDi below 5% under typical conditions. Actual results depend on filter capacity, load spectrum, background distortion and the measurement point. Verify the outcome at the agreed point under comparable loads before and after filtering.
Does Sucyc-AHF support N+1 redundancy?
Yes. The series supports N and N+1 configurations. In an N+1 design, confirm that the remaining modules can meet the required compensation current when one module is unavailable.
Should I use open-loop or closed-loop CT sensing?
The series supports either configuration. Select the sensing arrangement according to the measurement boundary and parallel control design, then confirm CT and communication requirements against the approved documentation.
How many modules fit in one cabinet?
One cabinet supports up to five modules and up to 1,000 A, depending on the selected voltage and module ratings. Confirm the actual capacity against the configuration and cabinet cooling requirements.
How is an AHF sized?
Size an active harmonic filter (AHF) from measured harmonic currents. Verify system voltage, wiring and the harmonic orders that need compensation.
Request a project quote
- System voltage, wiring and intended connection point
- Measured load current and harmonic spectrum
- Existing filtering or compensation equipment