Solar PV DC Surge Protection

Select a photovoltaic surge protective device (SPD) using the maximum string open-circuit voltage, DC cable route and inverter requirements.

Photovoltaic array installation
Application reference photo

PV DC protection points and SPD selection

Consider a grid-connected PV array without battery storage. Outdoor string cables run to the inverter. Review surge protection at the inverter DC input and assess whether the array or combiner needs additional protection given the cable route and the site lightning protection design.

  1. Mark the PV DC protection points

    Use the single-line diagram to locate the array, any combiner and the inverter DC input. Record the DC cable routes, existing SPDs and the inverter manufacturer’s surge protection requirements.

  2. Check the PV SPD against the string data

    Determine the maximum string open-circuit voltage at the lowest design temperature. For SCD20E P312PV, confirm the maximum continuous PV operating voltage (Ucpv), voltage protection level (Up) and applicable PV short-circuit current in the product documentation before choosing it.

  3. Coordinate protection across the array and inverter

    Review any built-in inverter protection, the site earthing design and the required SPD type at each point. Assess the inverter AC output as a separate circuit.

Verify PV SPD locations and string voltage

At handover, verify the installed PV SPD models and locations against the approved drawing and string voltage calculation. Record the status of each SPD and include the inverter’s built-in protection and any additional PV SPDs in the maintenance checklist.

Prepare a project enquiry

  • PV single-line diagram with array, combiner and inverter locations, plus DC cable routes
  • Module specifications, modules per string and the minimum design temperature
  • Inverter protection requirements, site earthing design and existing SPD models